Technical Notice V1.0 / 01.09 Page 93 / 100
Breakdowns 13
The motor doesn't run
- Check the rotation direction.
- Circuit breaker activated
Check the liquid level.
Reset the circuit breaker.
- Faulty bearings
Replace the bearings.
- Insufficient fluid
Add some fluid.
- Non-standard fluid quality
Change the fluid.
- Motor out of order
Replace the motor.
The motor runs, but without the pressure increasing in the circuit concerned
- Faulty pump
Replace the pump
G. Check that the compressor is running
The compressor is powered on but doesn't work
- The internal compressor safety switch has been activated
Cut off the power supply
Let the unit cool off (may take several hours)
Restart the unit
Check that the exhaust fan is working properly
Clean the condenser
LP contact is open (optional on CSW50 through CSW150), intake pressure too low
for the compressor
- Gas leakage?
Call a refrigeration engineer to repair the leak and refill the circuit with gas
LP contact is open (optional), intake pressure too low for the compressor
- The breakdown is indicated on the breakdown indicator (starting at model CSW200)
Follow the instructions