temperature protection upon
inverter and stop in the stop mode
Tens place of LED: Action upon
under-voltage fault indication
0 : No action
1 : Action (under-voltage is
regarded as a kind of fault)
Hundreds place of LED: Action
upon auto-reset interval fault
indication
0 : No action
1 : Action
Thousands place of LED: Fault
lockup function selection
0 : Prohibited
1 : Open (without fault output)
2 : Open (with fault output)
P97.03
Overload
protection
setting for
motor
Overload
protection
setting
Unit place of LED: Overload
compensation mode
0: No action
1: Common motor (with
low-speed compensation)
2: Variable-frequency motor
(without low-speed
compensation)
Tens place of LED: Overload
pre-alarm detection selection
0: Always detect
1: Detect only at constant speed
Hundreds place of LED: Overload
pre-alarm action selection
0: Alarm and keep running
1: Activate protection and coast to
stop
Thousands place of LED:
Overload detection level selection
0: Relative to rated current of the
motor (Er.oL1)
1: Relative to rated current of the
drive (Er.oL2)
1 0001 × ×
P97.04
Overload
pre-alarm
detection
level
Overload
detection
level
20.0%~200.0% 0.1% 130.0% ×
P97.05
Overload
pre-alarm
detection
time
Overload
detection
time
0.0~60.0s 0.1s 5.0s ×