224
MV600 memorizes the latest 3 types of fault (P97.15, P97.16 and P97.17) and records the bus voltage
(P97.18), output current (P97.19), running frequency (P97.20) and running status (P97.21) of the 3rd
fault for your reference. For the corresponding relationships of the running status, please see P01.17.
The latest fault record is the record for the 3rd fault.
6.20 Drive parameters (Group P98)
The above are read-only parameters. Record the basic information of the drive. The values for
P98.03~P98.05 are set by the manufacturer.
This function code is used for setting the voltage level of the drive.
0: 220V
1: 380V
2: 400V
3: 415V
4: 440V
5: 460V
6: 480V
Drive series selection 0~6P98.06
Rated current 0~999.9AP98.05
Rated volta
g
e 0~999VP98.04
Rated ca
p
acit
y
0~999.9kVAP98.03
Use
r
-customized version No. 0~9999P98.02
Software version No. 0.00~99.99P98.01
Series No. 0~FFFF
(
600
)
P98.00
Drive o
p
eration status at the 3rd fault 0~FFFFH
(
0000
)
P97.21
O
p
eration fre
q
uenc
y
at the 3rd fault 0.00~3000.00Hz
(
0.00Hz
)
P97.20