The pre-magnetizing is used for creating the magnetic field before the startup of the asynchronous motor.
0: Operate automatically
Internal temperature detection program will be automatically started during the drive operation to
determine the operation of the fan according to the module temperature. If the fan is running before the
drive stop, the fan will run for another 3 minutes after the drive shuts down, and then the internal
temperature detection program will be started.
1: The fan keeps running when the power is on.
The fan keeps running after the drive is powered up.
2: Fun operates based on command
When the drive will operate normally upon receiving the running command, the fan will also operate.
When the drive stops running, so does the fan.
6.14 Multi-stage reference and simple PLC parameters (Group P13)
0: Multi-stage frequency reference
As a frequency mode, it is applied to multi-speed operation mode and simple PLC operation mode.
1: Multi-stage closed loop reference
As a voltage reference, it is applied to the process PID operation mode.
Multi-sta
g
e reference 11 -100.0~100.0%
(
60.0%
)
P13.11
Multi-sta
g
e reference 10 -100.0~100.0%
(
40.0%
)
P13.10
Multi-sta
g
e reference 9 -100.0~100.0%
(
20.0%
)
P13.09
Multi-sta
g
e reference 8 -100.0~100.0%
(
10.0%
)
P13.08
Multi-sta
g
e reference 7 -100.0~100.0%
(
100.0%
)
P13.07
Multi-sta
g
e reference 6 -100.0~100.0%
(
90.0%
)
P13.06
Multi-sta
g
e reference 5 -100.0~100.0%
(
80.0%
)
P13.05
Multi-sta
g
e reference 4 -100.0~100.0%
(
60.0%
)
P13.04
Multi-sta
g
e reference 3 -100.0~100.0%
(
40.0%
)
P13.03
Multi-sta
g
e reference 2 -100.0~100.0%
(
20.0%
)
P13.02
Multi-sta
g
e reference 1 -100.0~100.0%
(
10.0%
)
P13.01
Multi-sta
g
e reference
p
ro
p
ert
y
settin
g
0~1
(
0
)
P13.00
Reserved 0~65535
(
0
)
P12.19
Reserved 0~65535
(
0
)
P12.18
Reserved 0~65535
(
0
)
P12.17
Reserved 0~65535
(
0
)
P12.16
Reserved 100~400
(
0
)
P12.15
Coolin
g
fan control 0~1
(
2
)
P12.14
Low intensit
y
ma
g
netic control mode 0~2
(
1
)
P12.13
Low intensit
y
ma
g
netic ad
j
ustment coefficient 2 0~10000
(
1000
)
P12.12
Low intensit
y
ma
g
netic ad
j
ustment coefficient 1 0~10000
(
1000
)
P12.11
Minimum flux reference value 10~150 %
(
10%
)
P12.10