P13.17, P13.19, P13.21, P13.23, P13.25, P13.27, P13.29, P13.31, P13.33, P13.35, P13.37, P13.39,
P13.41, P13.43 and P13.45 are used to configure the running frequency, direction, acceleration /
deceleration time for each stage of the PLC, and they are selected by bits. As shown in Fig.6-71.
UnitTensHundreds
Frequency setting:
0: Select the multi-stage frequency
1: Keyboard reference
2: Terminal UP/DOWN reference
3: Reserved
4: AI reference
5: PULSE reference
6: PID
7: Reserved
Running direction setting:
0:
FWD
1:
REV
2:Determined by running command
0: Acceleration/deceleration time1
Acceleration/deceleration time setting
1: Acceleration/deceleration time2
2: Acceleration/deceleration time3
3: Acceleration/deceleration time4
∨∧
Fig. 6-71 Setting of PLC stage
Unit place of LED setting of the PLC i stage:
0: Select the multi-stage frequency i
For example, when i=3, the frequency of stage 3 is the multi-stage frequency 3. For the definition of the
multi-stage frequency, please refer to P13.00~P13.46.
1: Digital reference 1: Keyboard ∧∨ reference
2: Digital reference 2: Terminal UP/DN reference
3: Serial port communication reference
4: AI analog reference
The function code P10.01 shall be set for AI analog reference. 1 or 9 shall be set for this terminal function
according to input analog signal (Their directions are all determined by LED’s tens place setting of PLC
current stage).
5: Terminal PULSE reference
The frequency setting is confirmed by the terminal pulse frequency and it can be input only by X7 and X8.
for details, please refer to definition in the function code of Group P09.
6: Process closed loop PID
Note
When the stage running direction of PLC is determined by running command, the running direction of motor
can be changed from external direction command in real time. For example, the forward and reverse running
Sta
e 15 runnin
time 0.0~6500.0
20.0
P13.46
Sta
e 15 settin
0~327H
000