EasyManua.ls Logo

Metasphere MM-IM - Page 19

Default Icon
85 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MM-IM User Guide
19
You can choose either Modbus on Ethernet, or Serial Modbus-RTU. The format of the
“Com port” string must be in lower case as shown in the example below. It comprises:
<COM port>, <Baud rate>, <parity>, <Data bits>, <Stop bits>
Note: If configuring Modbus for COM4 (RS485), you must add an extra item to the
“Com port” string: rs485. E.g. com4,19200,n,8,1,rs485. This must be in lower case.
Once you have inserted the port, you can then right click on it and choose “Insert
Slave/Data Block. Fill in the details as required. An example is shown below.

Table of Contents