37
Table 6: Device and communication register
Read Only (Function 0x03 or 0x04)
0-1 Reserved
2-3 Device Type
4-5 Version
Read Only (Function 0x03 or 0x04)
1000 Device ID 1-255
1001 Parity 1=none 2=even
3=odd
1002 Baudrate 1=2400
2=4800
3=9600
4=19200
5=38400
Table 7: Operation data registers
Read Only (Function 0x03 or 0x04)
Register Description Type
Min.
Unit
Range
4000-
4001
Negative Real
Energy
dword 1kWh 0~1000000M
4002-
4003
Positive Real Energy dword 1kWh 0~1000000M
4004-
4005
Reserved
4006-
4007
Apparent Energy dword 1kVAh 0~1000000M

Related product manuals