40
Read Only (Function 0x03 or 0x04)
Register Description Type
Min.
Unit
Range
4058-
4059
Total Demand
Reactive Power
int 1VAR -2000M~2000M
4060-
4061
Max.Total Demand
Reactive Power
int 1VAR -2000M~2000M
4062-
4063
Reserved
4064-
4065
Total Demand Real
Power
int 1W -2000M~2000M
4066-
4067
Max. Total Demand
Real Power
int 1W -2000M~2000M
4068-
4069
Reserved
4070-
4071
Total Demand
Apparent Power
dword 1VA 0~2000M
4072-
4073
Max. Total Demand
Apparent Power
dword 1VA 0~2000M
4074-
4075
Reserved
4076
Displacement Power
Factor L1
word 0.001 0 ~ 1.000
4077
Displacement PF
sign L1
word -
0=Resistive;
1=ind; 2=cap
4078
Displacement Power
Factor L2
word 0.001 0 ~ 1.000
4079
Displacement PF
sign L2
word -
0=Resistive;
1=ind; 2=cap
Table 7: Operation data register (cont)