Page 116 Accumass BW500 PL-565
Communication
P771 protocol address
Note:
Applicable only to ports programmed for Modbus RTU or Modbus ASCII
(Parameter 770).
The unique identifier of the BW500 on the network for the selected port, ports 1 to 3
(P771-01 to 03).
For devices connected with the Milltronics protocol this parameter is ignored.
For devices connected with a serial Modbus protocol this parameter is a number from
1-247. It is up to the network administrator to ensure that all devices on the network
have unique addresses.
Do not use the value 0 for Modbus communications as this is the broadcast address
and is inappropriate for a slave device.
Values
0 to 9999 (f = 1)
P772 Baud Rate
The communication rate with the master device for the selected port, ports 1 to 3
(P772-01 to 03).
The baud rate chosen should reflect the speed of the connected hardware and
protocol used.
Values
1 4800 baud
2 9600 baud
3 19,200 baud
f-03
4 38,400 baud
P773 Parity
The serial port parity for the selected port, ports 1 to 3 (P773-01 to 03).
Ensure that the communications parameters are identical between the BW500 and all
connected devices.
For example many modems default to N-8-1 which is No parity, 8 data bits, and 1
stop bit.
Values
0
none
f
1even
2 odd