Page 78 Accumass BW500 PL-565
Parameters
Totalization (P619 - P648)
The following parameters are specific to the use to the BW500 totalizers. Refer also
to Operation \ Totalization.
P619 Totalling Dropout
This parameter sets the limit, in percent of design load, below which material rates
are not totalized. (f=3.0)
The value of '0' is reserved to allow both negative and positive totalization.
Enter drop out value in % of design load
P631 Totalizer Resolution
This parameter sets the resolution of the totalizer selected.
Totalizers are:
-01, totalizer 1
-02, totalizer 2
-03, verification totalizer
-04, material test totalizer
-05, batch totalizer
Entry:
1 = 0.001 (one thousandth)
2 = 0.01 (one hundredth)
3 = 0.1 (one tenth)
4 = 1 (unit)
f
5 = 10 (x ten)
6 = 100 (x hundred)
7 = 1000 (x thousand)
P635 Verification Totalizer
Enables a dedicated internal totalizer that totals the amount of material conveyed
during a zero or span verification. It is used to verify the accuracy of the scale.
If a printer is connected to a port and the required programming is in order, a printout
of the activity is automatically done on completion of the verification process.