PL-565 Accumass BW500 Page 77
Parameters
e.g.
1
st
batch 2
nd
batch 3
rd
batch
setpoint
1000 1000 1000
pre-act
1000 950 960
total
1050 990 1000
P569 Manual Batch Pre-Act Amount
Enter a value to make the setpoint relay change state at a known value lower than
the setpoint (P564).
e.g. Setpoint = 1000
Manual Pre-Act = 50
The setpoint relay will activate when the batch totalizer reaches 950.
P598 Span Adjust Percentage
Accessible only through manual span adjust (P019), when percent change (1) is
selected.
Refer to % Change on page 42.