PL-565 Accumass BW500 Page 81
Parameters
ECal Parameters (P693 – P698)
Accessible only through P017 for ECal test reference. After Ecal completion, only a
zero calibration is necessary to allow access to the run mode.
P693 Belt Scale Model
Selects the model of the belt scale connected to the BW500.
Entry:
1 = MUS
2 = MSI
f
3 = MMI
4 = other*
*in the case of other, software jumps to P699 since data entry P694 through P698
are not applicable if P693=4
P694 ECal Load Cell Capacity
Enters the load cell’s weighing capacity for the selected cell. (f=1.0)
-01 = load cell A
-02 = load cell B
-03 = load cell C*
-04 = load cell D*
*applicable only if P693=3
Enter the value in the units corresponding to the scale selection, e.g. in kg if P693 =
1, or lb if P693 = 2 or 3.
P695 ECal Load Cell Sensitivity
Enters the load cell’s sensitivity for the selected cell. (f=1.0)
-01 = load cell A
-02 = load cell B
-03 = load cell C*
-04 = load cell D*
*applicable only if P693=3
Enter the value in mV/V obtained from load cell nameplate
P696 ECal Load Cell Excitation
Determines the excitation applied to the load cells. (f=10.00)
Nominally this value is 10 V. However, a measurement of the voltage at the load cell
provides the most accurate entry.
Enter the load cell excitation in volts dc.