PL-565 Accumass BW500 Page 75
Parameters
P415 Local Setpoint Value
Sets the local setpoint (P415-01 / 02), in engineering units, for the corresponding PID
system (1 or 2) when in auto mode. For the external process variable, the setpoint is
shown is %. (f=0.000)
P416 External Setpoint
Displays the external setpoint (P416-01 / 02), in engineering units, for the
corresponding PID system (1 or 2). For the external process variable, the setpoint is
shown is %.
If the setpoint is external (P414 = 1 or 2), then this parameter displays the setpoint
value that is being input, either mA input 1 or 2.
P418 Remote Setpoint Ratio
Sets the remote setpoint ratio (P418 –01/02) for the corresponding PID system (1 or
2) when P414 = 1 or 2. (f=100)
The remote setpoint ratio scales remote setpoint input by the set percentage. A value
of 100 means that the setpoint is 100% of the mA input.