Page 86 Accumass BW500 PL-565
Parameters
P943 Load Cell A/D Reference
Displays the A/D reference value for the selected load cells. These values are
affected by load cell balancing (P295).
Load cells are:
01 = A and B
02 = C and D
03 = A and B plus C and D
04 = A
05 = B
06 = C
07 = D
P948 Error Log
Displays a log of the last 25 error or alarm events (P948 01 to 25) that have
occurred. Event 01 is the current error.
Display:
0 = no error
# = error code, refer to Troubleshooting on page 137
P949 Diagnostic Error Testing
Enables or disables diagnostic error checking for memory, load cell and zero speed.
(f=0)
Entry:
0 = disable
1 = enable
Refer to Troubleshooting on page 137.
P950 Zero Register
Registers the number of zero calibrations that have been done since the last master
reset. (f=0)
P951 Span Register
Registers the number of span calibrations for the span selected, span 1 to 4 (P951 -
01 to - 04), that have been done since the last master reset. (f=0)
P952 Design Load
Displays the value of the design load, which corresponds to the full scale value for
alarm and mA output functions. The design load is calculated, based on the design
rate and design speed. (f=0.00)