10 TEST FUNCTION
10.1 External Input/Output Forced On/Off Function
Forced on/off timing
The following table lists the timing to reflect the registered data in the forced on/off registration settings to the input/output
devices or external outputs.
*1 For the precautions for using the direct access device, refer to the following.
Page 156 Precautions
*2 At input/output refresh execution where input/output refresh is registered for each program, and for interrupt programs.
*3 When an output device or external output is specified as a refresh device in multiple CPU refresh and the forced on/off function is
executed, the device is not forcibly turned on or off.
Checking the forced on/off execution status
The execution status of the forced on/off can be checked in the following ways.
Engineering tool
The execution status can be checked with the [Update Status] button of the engineering tool. ( Page 152 Operation
method of forced on/off)
FUNCTION LED
The FUNCTION LED of the CPU module flashes by registering forced on/off (every 200ms).
The LED indicator follows the status of the external input/output forced on/off function even when the LED
Display Setting has been set and other functions that use the FUNCTION LED are being executed. (
Page 131 LED display setting)
The display status of the FUNCTION LED can be checked with "Module Information List" in the module diagnostics. ( GX
Works3 Operating Manual)
Inputs/outputs for which forced on/off
can be set
Reflection timing for the input devices Reflection timing for the output devices or
external outputs
Input/output of the modules mounted on the
base unit
END processing (at input refresh)
At COM instruction execution (at input refresh)
At instruction execution using the direct access
input (DX) (LD, LDI, AND, ANI, OR, ORI, LDP,
LDF, ANDP, ANDF, ORP, ORF, LDPI, LDFI,
ANDPI, ANDFI, ORPI, ORFI)
*1
At execution of the RFS instruction and MTR
instruction
At execution of instructions used in the interrupt
by the system (UDCNT1, UDCNT2, SPD)
At program execution
*2
At execution of the inter-module synchronization
cycle program (I44)
At execution of the multiple CPU synchronization
program (I45) and non-execution of the multiple
CPU synchronization program (I45) (at END
processing)
*3
END processing (at output refresh)
At COM instruction execution (at output refresh)
At instruction execution using the direct access
output (DY) (OUT, SET, DELTA(P), RST, PLS,
PLF, FF, MC, SFT(P))
*1
At execution of the RFS instruction and MTR
instruction
At execution of instructions used in the interrupt
by the system (PLSY, PWM)
At program execution
*2
At execution of the inter-module synchronization
cycle program (I44)
Input/output of the CPU module assigned to LX
and LY of the CC-Link IE Controller Network
module or MELSECNET/H module
END processing (at link refresh of the CC-Link IE Controller Network module or MELSECNET/H module)
At COM instruction execution (at link refresh of the CC-Link IE Controller Network module or
MELSECNET/H module)
At ZCOM instruction execution (at link refresh of the CC-Link IE Controller Network module or
MELSECNET/H module)
Input/output of the CPU module assigned to RX
and RY of the CC-Link module
END processing (at link refresh)
At COM instruction execution (at link refresh)
At ZCOM instruction execution (at link refresh)
Input/output of the CPU module assigned to RX
and RY of the CC-Link IE Field Network module
END processing (at link refresh)
At COM instruction execution (at link refresh)
At ZCOM instruction execution (at link refresh)
At execution of the inter-module synchronization cycle program (I44)
Input/output of the CPU module assigned to RX
and RY of the CC-Link IE Field Network Basic
END processing (at link refresh)
At COM instruction execution (at link refresh)