180
11 DATA LOGGING FUNCTION
11.3 Logging Type
Specifying the monitored data
For the device and label change specification, monitored data can be configured to be collected from the devices and labels
listed in the following table.
*1
*1 When specifying the local device, global label, or local label, check the versions of the CPU module, engineering tool, and CPU Module
Logging Configuration Tool. ( Page 1008 Added and Enhanced Functions)
The data types that can be selected include bit/word (unsigned), word (signed), double word (unsigned), and double word
(signed). If double word (unsigned) or double word (signed) is specified, a trigger occurs only when as much data as one
double word is written. No trigger occurs when only the upper or lower word of a double word is written.
*2 An index modified device and indirectly specified device cannot be specified.
*3 For bit devices, digit specification is not supported.
*4 For word devices, bit specification is allowed.
*5 To specify the local device, use "Program name/#Device name". (Example: "MAIN/#M1")
*6 To specify these devices with CPU Module Logging Configuration Tool, use T (contact): TS, ST (contact): STS, C (contact): CS, LT
(contact): LTS, LST (contact): LSTS, and LC (contact): LCS.
*7 A label with a name of 256 characters or less can be specified. When the local label is specified (program block name/label name), the
"program block name/" part is counted as the number of characters.
*8 Only labels in the read project of the engineering tool can be specified.
*9 Specify the label with "Program block name/Label name". (Example: "ProgPou/label_w1")
*10 Digit-specified labels cannot be specified.
*11 Bit specification is allowed.
*12 Only the contacts and current values can be specified.
*13 For the label of timer type and counter type, specify the element name. (S: contact, N: current value)
Global label example: "label_w1.S"
Local label example: "ProgPou/label_w1.S"
*14 Specify the array element. If the array element is not specified, it is handled as the start of the array ([0]). ( Page 969 Data)
*15 Specify the structure member. ( Page 969 Data)
Type Device
*2
Device Bit device
*3
X, Y, M
*5
, L, F, SM, V
*5
, B, SB, T (contact)
*5*6
, ST (contact)
*5*6
, C (contact)
*5*6
, LT
(contact)
*5*6
, LST (contact)
*5*6
, LC (contact)
*5*6
, FX, FY
Word device
*4
T (current value)
*5
, ST (current value)
*5
, C (current value)
*5
, D
*5
, SD, W, SW, RD, R, ZR, Z, FD
Double-word device LT (current value)
*5
, LST (current value)
*5
, LC (current value)
*5
Type Class Data type
Label
*7*8
Global label VAR_GLOBAL
VAR_GLOBAL_RETAIN
Primitive data type/array
*14
•Bit
*10
Word (signed)
*11
Double word (signed)
Word (unsigned)
*11
Double word (unsigned)
Timer type
*12*13
Retentive timer type
*12*13
Counter type
*12*13
Long timer type
*12*13
Long retentive timer type
*12*13
Long counter type
*12*13
Structure
*15
Local label
*9
•VAR
VAR_RETAIN