APPX
Appendix 1 Error Codes
739
A
3140H END instruction
error
The END (FEND) instruction does
not exist in the program.
Stop Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
Take measures to reduce noise.
Write the sequence program(s) and FB
program(s) to the CPU module again.
Then, reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Error location
information
At power-on,
at RESET, at
STOP RUN
state
3141H FB/FUN
program error
The structure of FB/FUN program
is incorrect.
Stop Take measures to reduce noise.
Write the sequence program(s) and FB
program(s) to the CPU module again.
Then, reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Error location
information
At instruction
execution
3142H Temporary area
error
The temporary area was used
incorrectly.
Stop Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and check the program.
Take measures to reduce noise.
Write the sequence program(s) and FB
program(s) to the CPU module again.
Then, reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Error location
information
At instruction
execution
3143H FB/FUN
program error
The FB/FUN program file is
incorrect.
Stop Take measures to reduce noise.
Write the sequence program(s) and FB
program(s) to the CPU module again.
Then, reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Error location
information
At instruction
execution
3160H
to
3163H
SFC program
block, step error
The SFC program configuration is
illegal.
Stop Take measures to reduce noise.
Write the SFC program to the CPU
module again. Then, reset the CPU
module and run it again. If the same
error code is displayed again, the
possible cause is a hardware failure of
the CPU module. Please consult your
local Mitsubishi representative.
Error location
information
At power-on,
at RESET, at
STOP RUN
state, at SFC
program
execution
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing