740
APPX
Appendix 1 Error Codes
3170H SFC program
block, step error
• The number of SFC program
steps exceeds the total number of
step relays (S).
Stop • Correct the program so that the
number of SFC program steps does
not exceed the total number of step
relays (S).
• Check and correct the number of
device setting step relays (S) in the
CPU parameters.
Error location
information
At power-on,
at RESET, at
STOP RUN
state, at SFC
program
execution
3171H SFC program
block, step error
• The total number of SFC program
blocks (max. step No. + 1)
exceeds the total number of step
relays (S).
Stop • Correct the program so that the total
number of SFC program blocks (max.
step No. + 1) does not exceed the total
number of step relays (S).
• Check and correct the number of
device setting step relays (S) in the
CPU parameters.
Error location
information
At power-on,
at RESET, at
STOP RUN
state, at SFC
program
execution
3180H SFC program
configuration
error
• The SFC program configuration is
illegal.
Stop • Take measures to reduce noise.
• Write the SFC program to the CPU
module again. Then, reset the CPU
module and run it again. If the same
error code is displayed again, the
possible cause is a hardware failure of
the CPU module. Please consult your
local Mitsubishi representative.
Error location
information
At power-on,
at RESET, at
STOP RUN
state, at SFC
program
execution
3190H At SFC
program
execution
3191H
3192H SFC program
configuration
error
• A self step number was specified
for the specification destination
step number for the jump
transition.
Stop • Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
• Take measures to reduce noise.
• Write the SFC program to the CPU
module again. Then, reset the CPU
module and run it again. If the same
error code is displayed again, the
possible cause is a hardware failure of
the CPU module. Please consult your
local Mitsubishi representative.
Error location
information
At SFC
program
execution
3193H • A self step number was specified
for the specification destination
step number for the reset step.
31A0H SFC program
block, step
specification
error
• An attempt was made to start an
SFC program block that was
already running.
Stop • Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
•
Turn on Start/stop SFC program
(SM321) if it is off.
Error location
information
At SFC
program
execution
31A1H SFC program
block, step
specification
error
• A non-existent SFC program block
was specified.
Stop • Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
• Turn on SM321 (Start/stop SFC
program) if it is off.
• Check the SFC program has existed.
• Check the execution status of the SFC
program.
Error location
information
At instruction
execution, at
SFC program
execution
31A2H SFC program
block, step
specification
error
• The specified block exceeds the
range that can be used in the SFC
program.
Stop • Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
• Turn on SM321 (Start/stop SFC
program) if it is off.
Error location
information
At instruction
execution
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic