APPX
Appendix 1 Error Codes
741
A
31B1H SFC program
block, step
specification
error
A non-existent SFC program step
was specified.
Stop Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
Turn on SM321 (Start/stop SFC
program) if it is off.
Check the SFC program has existed.
Check the execution status of the SFC
program.
Error location
information
At instruction
execution, at
SFC program
execution
31B2H SFC program
block, step
specification
error
The specified step exceeds the
range that can be used in the SFC
program.
Stop Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
Turn on SM321 (Start/stop SFC
program) if it is off.
Error location
information
At instruction
execution
31B3H SFC program
block, step
specification
error
The number of simultaneous
active block steps that can be
specified in the SFC program
exceeds the permissible value.
Stop Check the detailed information (error
location information) of the error by
executing module diagnostics using
the engineering tool, display the error
program (step) by clicking the [Error
Jump] button, and correct the program.
Error location
information
At instruction
execution, at
SFC program
execution
31B4H The total number of simultaneous
active steps that can be specified
in the SFC program exceeds the
permissible value.
At instruction
execution, at
SFC program
execution
31B5H A SET Sn/BLm/Sn and RST Sn/
BLm/Sn instruction were specified
for the self step in the step
operation output.
At instruction
execution
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing

Table of Contents