756
APPX
Appendix 1 Error Codes
37C1H Program
execution error
In the CPU module which
operates in redundant mode, an
SFC program is set in the CPU
parameters ("Program Setting").
Stop Check the detailed information (drive/
file information) of the error by
executing module diagnostics using
the engineering tool, and delete all
SFC programs registered. Then, write
CPU parameters to the CPU module
again.
Drive/file
information
At write, at
power-on, at
RESET, at
STOP RUN
state
37E0H Memory format
by memory copy
The memory copy was executed
and the memory in the standby
system has been formatted.
Stop Power off and on or reset the CPU
module after the memory copy
completed.
At memory
copy
3C00H Hardware failure A hardware failure has been
detected.
Stop CPU module
Take measures to reduce noise.
Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Redundant function module
The possible cause is malfunction due
to noise. Take measures to reduce
noise by checking the distance of wires
and cables, and the grounding status of
each device.
Execute a module communication test.
If the same error code is displayed
again, the possible cause is a
hardware failure of the redundant
function module. Please consult your
local Mitsubishi representative.
Failure
information
Always
3C01H
3C02H At power-on,
at RESET, at
END
instruction
execution, at
interrupt
occurrence
3C03H Always
3C0FH CPU module
Take measures to reduce noise.
Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module,
extended SRAM cassette, battery-less
option cassette, or module (SIL2
function module or safety function
module) connected. Please consult
your local Mitsubishi representative.
Redundant function module
The possible cause is malfunction due
to noise. Take measures to reduce
noise by checking the distance of wires
and cables, and the grounding status of
each device.
Execute a module communication test.
If the same error code is displayed
again, the possible cause is a
hardware failure of the redundant
function module. Please consult your
local Mitsubishi representative.
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing

Table of Contents

Related product manuals