APPX
Appendix 1 Error Codes
757
A
3C10H Hardware failure A hardware failure has been
detected.
Stop CPU module
Take measures to reduce noise.
Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Redundant function module
The possible cause is malfunction due
to noise. Take measures to reduce
noise by checking the distance of wires
and cables, and the grounding status of
each device.
Execute a module communication test.
If the same error code is displayed
again, the possible cause is a
hardware failure of the redundant
function module. Please consult your
local Mitsubishi representative.
Failure
information
At power-on,
at RESET
3C11H At END
instruction
execution, at
instruction
execution
3C12H Hardware failure The waveform of the voltage out
of the specified range has been
detected in the power supply
module.
A hardware failure has been
detected in the power supply
module, CPU module, base unit,
or extension cable. (In a
redundant power supply system,
the error is detected when two
power supply modules failed.)
Stop Check the waveform of the voltage
applied to the power supply module.
Check the mounting status of the CPU
module.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the power supply
module, CPU module, base unit, or
extension cable. Please consult your
local Mitsubishi representative.
Failure
information
Always
3C13H Hardware failure A hardware failure has been
detected.
Stop Take measures to reduce noise.
Check the mounting status of the CPU
module.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module.
Please consult your local Mitsubishi
representative.
Failure
information
Always
3C14H Hardware failure A hardware failure has been
detected.
Stop Take measures to reduce noise.
Check the mounting status of the CPU
module.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module.
Please consult your local Mitsubishi
representative.
Failure
information
Always
3C15H Hardware failure A hardware failure has been
detected.
Stop Take measures to reduce noise.
Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible cause is
a hardware failure of the CPU module
or module (SIL2 function module or
safety function module) connected.
Please consult your local Mitsubishi
representative.
Failure
information
At END
instruction
execution, at
power-on, at
RESET
3C16H
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing

Table of Contents