758
APPX
Appendix 1 Error Codes
3C17H Hardware failure • A hardware failure has been
detected.
Stop • Take measures to reduce noise.
• Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
• Format the memory. Write all files to
the CPU module. Then, reset the CPU
module and run it again If the same
error code is displayed again, the
possible cause is a hardware failure of
the CPU module or module (SIL2
function module or safety function
module) connected. Please consult
your local Mitsubishi representative.
Failure
information
Always
3C20H Memory error • An error has been detected in the
memory.
At power-on,
at RESET
3C21H At END
instruction
execution, at
power-on, at
RESET
3C22H
3C2FH ■CPU module, SIL2 function module,
safety function module
• Take measures to reduce noise.
• Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
• Format the memory. Write all files to
the CPU module. Then, reset the CPU
module and run it again If the same
error code is displayed again, the
possible cause is a hardware failure of
the CPU module or module (SIL2
function module or safety function
module) connected. Please consult
your local Mitsubishi representative.
■Redundant function module
• Execute a module communication test.
If the same error code is displayed
again, the possible cause is a
hardware failure of the redundant
function module. Please consult your
local Mitsubishi representative.
Always
3C30H Memory error • An error has been detected in the
memory.
Stop • Take measures to reduce noise.
• Check the mounting status of the CPU
module, SIL2 function module, and
safety function module.
• Format the memory. Write all files to
the CPU module. Then, reset the CPU
module and run it again If the same
error code is displayed again, the
possible cause is a hardware failure of
the CPU module or module (SIL2
function module or safety function
module) connected. Please consult
your local Mitsubishi representative.
Failure
information
At instruction
execution
3C31H Always
3C32H
3C33H At power-on,
at RESET
3C34H Memory error • An error has been detected in the
memory.
Stop • Take measures to reduce noise.
• Check the mounting status of the CPU
module.
• Format the memory. Write all files to
the CPU module. Then, reset the CPU
module and run it again. If the same
error code is displayed again, the
possible cause is a hardware failure of
the CPU module. Please consult your
local Mitsubishi representative.
Failure
information
At power-on,
at RESET
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing