APPX
Appendix 1 Error Codes
767
A
40D0H Label
communication
error
The target CPU module does not support "Access from
External Device" of "Global Label Setting".
Disable "Access from External Device", and then write the
data to the programmable controller again.
4100H Any other error Hardware failure of the CPU module. Replace the CPU module.
4101H Any other error Serial communication connection was executed for a
different CPU module series.
Check the CPU module series.
4103H Any other error The instruction written by online program change is incorrect
or invalid.
Execute online program change again. Or, set the operating
status of the CPU module to STOP, and write the program.
4104H Any other error An instruction(s) that cannot be executed by the CPU
module set to process mode or redundant mode is included
in the instructions targeted for online program change.
Delete the instruction(s) that cannot be executed, and
execute the online program change function again. Or, set
the operating status of the CPU module to STOP, and write
the program.
4105H Any other error Hardware failure of the CPU module internal memory The possible cause is a hardware failure of the CPU module.
Please consult your local Mitsubishi representative.
4108H Any other error The device monitor/test cannot be performed normally. Execute the function again. Check that the access prohibited
area is not accessed, and execute the function again.
410AH Any other error The specified command cannot be executed because the
online program change is being executed.
When CPU Module Logging Configuration Tool is used
The data logging where a step No. is specified as the
collection start condition or trigger condition was started
during the online program change.
The data logging where a label (global label or local label) is
specified as the collection start condition, data collection
target, or trigger condition was started during the online
program change.
The data logging setting file where a label (global label or
local label) is specified as the collection start condition, data
collection target, or trigger condition was written during the
online program change.
Execute the request again after the online program change.
410BH Any other error The monitor condition registration was cleared after the
online program change was executed.
Execute the registration of monitoring condition again after
the online program change.
410CH Any other error Writing to the specified data is not supported. Check that the version of the engineering tool used is
correct.
Check the settings and make a correction.
410EH Any other error When the execution status of the online program change is
in error, the online program change command was issued.
Issue the online program change cancel command, and
execute the function again.
410FH Any other error During the execution of the online program change function,
the cancel command was issued by the same request
source.
Issue the command again after the currently-performed
processing ends.
4110H CPU module
error
The request cannot be executed because the CPU module
is in a stop error state.
Reset the CPU module and execute the request again.
4111H CPU module
error
The request cannot be executed because the other CPU
modules, except the host CPU module, have not yet started
in a multiple CPU system.
Execute the request again after all the other CPU modules
have started.
4121H File related error The specified drive (memory) or file does not exist. Execute again after checking the specified drive (memory)
or file.
4122H File related error The specified drive (memory) or file does not exist. Execute again after checking the specified drive (memory)
or file.
4123H File related error The specified drive (memory) is abnormal.
When CPU Module Logging Configuration Tool is used
The data logging was started to the memory having an error.
Initialize the memory, and restore the drive (memory) to its
normal state.
4124H File related error The specified drive (memory) is abnormal. Initialize the memory, and restore the drive (memory) to its
normal state.
4125H File related error The specified drive (memory) or file is performing
processing.
Execute again after a while.
4126H File related error The specified drive (memory) or file is performing
processing.
Execute again after a while.
4127H File related error File password mismatch Execute again after checking the file password.
4128H File related error File password mismatch with copy destination Execute again after checking the file password.
4129H File related error The request cannot be executed since the specified drive
(memory) is ROM.
Execute again after changing the target drive (memory).