APPX
Appendix 4 List of Special Relay Areas
805
A
*1 There are restrictions on the firmware version of the supported CPU module. ( Page 1008 Added and Enhanced Functions)
SM80 Detailed information 1: Flag
in use
Off: Not used
On: In use
This relay switches to on if the detailed
information n exists when SM0 switched to
on.
S (Status change) ALL
SM112 Detailed information 2: Flag
in use
ALL
SM150 Power-off/power supply
voltage drop detection
Off: Power-on/normal
power supply voltage
On: Power-off/voltage drop
detected/power supply
module not mounted
This relay turns on when one or more of
the power supply modules whose power
has been shut off or power supply voltage
has dropped (not including a momentary
power failure), or one or more of empty
slots for the power supply module are
detected on the redundant power supply
base unit.
This relay turns on if causes to turn on
any bits of SD150 have been occurred.
This relay turns off if causes to turn on
any bits of SD150 have been removed.
In a multiple CPU system, the flags are
stored only to the CPU No.1.
S (Status change) Rn
*1
RnP
RnPSF
SM151 Power supply module
failure detection
Off: Not detected/power-
off/no power supply
module
On: Detected
This relay turns on when one or more
power supply module failures have been
detected on the redundant power supply
base unit.
This relay turns on if causes to turn on
any bits of SD151 have been occurred.
This relay turns off if causes to turn on
any bits of SD151 have been removed.
In a multiple CPU system, the flags are
stored only to the CPU No.1.
S (Status change) Rn
*1
RnP
RnPSF
SM152 Momentary power failure
detection (power supply
module 1)
Off: Not detected
On: Detected
This relay turns on when a momentary
power failure of the input power supply to
the power supply 1 or 2 is detected one or
more times. After turning on, this relay
remains on even if the power supply
recovers from the momentary power
failure.
This relay turns off the flags (SM152 and
SM153) of the power supply 1 and 2
when the CPU module starts up.
When one of the two power supply
modules is powered off, this relay turns off
the corresponding flag to one powered
off.
In a multiple CPU system, the flags are
stored only to the CPU No.1.
S (Status change) Rn
*1
RnP
RnPSF
SM153 Momentary power failure
detection (power supply
module 2)
S (Status change) Rn
*1
RnP
RnPSF
SM154 Invalid power supply
module
Off: Valid/power-off/no
power supply module
On: Invalid
This relay turns on when one or more of
invalid power supply modules have been
detected on the redundant power supply
base unit.
This relay turns on if a factor to turn on
any bits of SD154 have been occurred.
This relay turns off if all the factors to turn
on any bits of SD154 have been removed.
In a multiple CPU system, the flags are
stored only to the CPU No.1.
S (Status change) Rn
*1
RnP
RnPSF
No. Name Data stored Details Set by (setting timing) CPU