Appendix 8  Buffer Memory
895
A
CC-Link IE Field Network Basic function
The following table lists buffer memory areas of the CPU module relating to the CC-Link IE Field Network Basic function. 
(Programmable controller CPU only)
Address Name Data stored Details Set by 
(setting 
timing)
Un\G1024 Total number of 
connected stations
Total number of 
connected stations
The total number of connected stations set in parameter is stored.
Range: 1 to 16
S (Initial)
Un\G1025 Reserved station 
specification status
Reserved station 
specification status
The reserved station specification status of the slave station specified 
in parameter is stored. (0: Not specified, 1: Specified)
b0: Reserved station specification status
b1 to b15: Empty (fixed to 0)
The station number that is specified as a reserved station can be 
checked in 'Reserved station specification status of each station' 
(Un\G1026).
S (Initial)
Un\G1026 
to 
Un\G1029
Reserved station 
specification status of 
each station
Reserved station 
specification status of 
each station
The reserved station specification status is stored using the following 
bit pattern. (Off: Other than the reserved station, On: Reserved station)
The numbers in the figure indicate station numbers.
(Condition)
• Only the bit of the start station number turns on.
• The status is not stored for the station numbers after the maximum 
station number.
S (Initial)
Un\G1030 Link scan information Group No.1 maximum 
link scan
The maximum link scan time value during cyclic transmission is stored. 
(Unit: ms)
S (Status 
change)
Un\G1031 Group No.1 minimum link 
scan
The minimum link scan time value during cyclic transmission is stored. 
(Unit: ms)
S (Status 
change)
Un\G1032 Group No.1 current link 
scan
The current link scan time value during cyclic transmission is stored. 
(Unit: ms)
S (Status 
change)
Un\G1034 Group No.2 maximum 
link scan
The maximum link scan time value during cyclic transmission is stored. 
(Unit: ms)
S (Status 
change)
Un\G1035 Group No.2 minimum link 
scan
The minimum link scan time value during cyclic transmission is stored. 
(Unit: ms)
S (Status 
change)
Un\G1036 Group No.2 current link 
scan
The current link scan time value during cyclic transmission is stored. 
(Unit: ms)
S (Status 
change)
Un\G1038 Group No.3 maximum 
link scan
The maximum link scan time value during cyclic transmission is stored. 
(Unit: ms)
S (Status 
change)
Un\G1039 Group No.3 minimum link 
scan
The minimum link scan time value during cyclic transmission is stored. 
(Unit: ms)
S (Status 
change)
Un\G1040 Group No.3 current link 
scan
The current link scan time value during cyclic transmission is stored. 
(Unit: ms)
S (Status 
change)
Un\G1042 Group No.4 maximum 
link scan
The maximum link scan time value during cyclic transmission is stored. 
(Unit: ms)
S (Status 
change)
Un\G1043 Group No.4 minimum link 
scan
The minimum link scan time value during cyclic transmission is stored. 
(Unit: ms)
S (Status 
change)
Un\G1044 Group No.4 current link 
sca
n
The current link scan time value during cyclic transmission is stored. 
(Unit: ms)
S (Status 
change)
Un\G1050 Diagnostic information 
display request
Diagnostic information 
display request
After the END instruction of the scan where the bit 0 is turned off and 
on is executed, the diagnostic information of a slave station specified in 
'Diagnostic request information' (Un\G1051) is read to Un\G1052 to 
Un\G1077.
When reading of the diagnostic information has completed at END 
processing, 0 is stored.
b0: Diagnostic information display request
b1 to b15: Empty (fixed to 0)
S (Status 
change)
*1
/U
b0
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17
48 47 46 45 44 43 42 41 40 39 38 37 36 35 34 33
64 63 62 61 60 59 58 57 56 55 54 53 52 51 50 49
b15 b14 b13 b12 b11 b10 b9 b8 b7 b6 b5 b4 b3 b2 b1 b0
Un\G1026
Un\G1027
Un\G1028
Un\G1029
b0