986
APPX
Appendix 13 How to Use CPU Module Logging Configuration Tool
Writing the logging setting
The following procedure is to write the data logging setting to the target memory.
Operating procedure
1. Open the "Write Logging Setting" window.
[Online] [Write Logging Setting]
2. Select the memory where the data to be written is stored from "Target Memory" list.
3. Select the checkbox corresponding to the data item to be written in the "Target logging setting data" list, and click the
[Write] button.
*1*2
*1 In backup mode of the Process CPU (redundant mode), data can be written to both systems or one of the systems. Click the [Write]
button and a window appears. Select whether or not to write data to both systems.
*2 The data logging setting using the function memory as the data storage destination memory cannot be written to the SD memory card.
Therefore, the setting is not displayed when "Memory card (SD)" is selected for "Target memory".
Window
Displayed items
Any existing data (data logging setting with the same setting number or common setting) on the target is
overwritten.
Item Description
Target Memory Select the memory where the data to be written is stored.
Target logging setting data Select the data to be written.