1 CPU MODULE
29
1
No. Name Description
(1) READY LED Indicates the operating status of the CPU module and the error level. ( Page 533 LED status of the CPU
module)
READY LED-ERROR LED status
On-off: Normal operation
On-on: Minor error
On-flashing: Moderate error
Flashing-on: Minor error (Changing module online)
Flashing (every 2s)-off: Initial processing
Flashing (every 400ms)-off: Changing module online
Off-on/flashing: Major error
(2) ERROR LED
(3) PROGRAM RUN LED Indicates the operating status of the program.
On: Being executed (RUN state)
Flashing: Being suspended (PAUSE state)
Off: Stopped (STOP state) or stop error
PROGRAM RUN LED
WHEN USING THE PROCESS
CPU (REDUNDANT MODE)
Indicates the operating status of the program.
Control system (CTRL LED of the redundant function module: On)
On: Being executed (RUN state)
Flashing: Being suspended (PAUSE state)
Off: Stopped (STOP state) or stop error
Standby system (SBY LED of the redundant function module: On)
[Backup mode]
On: Being executed (RUN state) (programs being executed in both systems)
Flashing: Being suspended (PAUSE state) (programs being executed in both systems)
Off: Stopped (STOP state/RUN state/PAUSE state) (no program being executed in both systems) or stop error
[Separate mode]
On: Being executed (RUN state)
Flashing: Being suspended (PAUSE state) or waiting for state transition to RUN (same as STOP state)
Off: Stopped (STOP state) or stop error
Control or standby system has not been determined yet
Flashing: Waiting for state transition to RUN by switch operation (same as STOP state)
Off: Normal operation
(4) USER LED Indicates the status of the annunciator (F). ( Page 453 Annunciator (F))
On: Annunciator (F) ON
Off: Normal operation
(5) BATTERY LED Indicates the battery status.
Flashing: Battery low
Off: Normal operation
(6) CARD READY LED Indicates the availability of the SD memory card.
On: Available
Flashing: Ready
Off: Not available or not inserted
(7) CARD ACCESS LED Indicates the access status of the SD memory card.
On: Being accessed
Off: Not accessed
(8) FUNCTION LED Turns on or flashes when the following functions are used:
LED setting
External input/output forced on/off function
Program restoration information write
Device test with execution condition
For the LED status, refer to the description of each function.
Page 206 LED display setting
(9) SPEED LED Refer to the following.
MELSEC iQ-R Ethernet/CC-Link IE User's Manual (Startup)
(10) SD/RD LED
(11) RUN/STOP/RESET switch A switch for controlling the operating status of the CPU module. ( Page 52 Executing the Program)
RUN: Executes the program.
STOP: Stops the program.
RESET: Resets the CPU module. (Keep the switch in the RESET position for approximately one second.)
Operate the RUN/STOP/RESET switch with your fingers. To prevent the switch from being damaged, do not use
any tool such as a screwdriver.
(12) SD CARD OFF button A switch for disabling access to the SD memory card to remove it from the CPU module ( Page 40 Inserting
and Removing an SD Memory Card)
(13) SD memory card slot A slot where an SD memory card is inserted
(14) USB port
*1
A connector for a USB-compatible peripheral (connector type: miniB)
(15) Ethernet port Refer to the following.
MELSEC iQ-R Ethernet/CC-Link IE User's Manual (Startup)

Table of Contents