398
26 REDUNDANT FUNCTION
26.3 Tracking Transfer
■Detailed setting
Set devices and labels to be transferred for each tracking block (No.1 to 64) to be used.
[CPU Parameter] [Redundant System Settings] [Tracking Setting] [Device/Label Detailed Setting]
*1 Global labels with devices assigned are not transferred as global labels. They are transferred according to the tracking settings of the
assigned devices.
When setting devices and labels for tracking transfer, click the [Size Calculation] button to check if the tracking
data capacity in one scan is equal to or less than 1M words. ( Page 404 Data capacity for tracking
transfer)
Item Item Description Setting
range
Default
Device Detailed
Setting
Global Device Setting Set global devices to be transferred. ( Page 399 Global device
setting)
0.0K Word
Local Device Setting Set whether to transfer local devices or not.
When "Transfer" is set, all the local devices are transferred.
For the devices that can be set as local devices, refer to the following.
Page 390 Devices that can be specified
•Do Not
Transfer
•Transfer
Do Not
Transfer
Label Detailed
Setting
Global Label Setting
*1
Set whether to transfer global labels or not.
When "Transfer" is set, all the global labels assigned to the device/label
memory are transferred.
•Do Not
Transfer
•Transfer
Do Not
Transfer
Local Label Setting Set whether to transfer local labels or not.
When "Transfer" is set, all the local labels are transferred.
•Do Not
Transfer
•Transfer
Do Not
Transfer
Module Label (Extension)
Setting
Set whether to transfer module labels of the modules on the extension
base unit for each tracking block or not. When "Transfer" is set, the
range that was set for the refresh target on the module label in the
refresh settings parameter for each module is transferred.
•Do Not
Transfer
•Transfer
Do Not
Transfer
Block Size Setting Calculates "Block Size Setting" of each tracking block and "Total" of the
setting capacity.