36 ERROR CODES
36.4 List of Error Codes
553
36
1031H Power supply
module
configuration
error
A power supply module other than the
redundant power supply module has
been mounted on the redundant
power supply base unit.
Continue Mount only applicable power
supply modules. If the same error
code is displayed again, the
possible cause is a hardware
failure of the power supply
module. Please consult your local
Mitsubishi representative.
System
configuration
information
Always
1080H ROM write
count error
The number of writes to the flash
ROM (data memory, program
memory, and system memory
(memory used by the system when
the CPU module executes its
function)) exceeded 100000 times.
Files are frequently written by the
event history function.
Continue Replace the CPU module. Frequency
information
At power-on, at
RESET, at
write
1090H Battery error The voltage of the battery built in the
CPU module has dropped below the
specified value.
The connector of the battery built in
the CPU module is disconnected.
The connector of the battery built in
the CPU module is not securely
connected.
Continue Replace the battery.
Connect the battery connector to
use the file storage area in the
device/label memory or the latch
function.
Check the connection status of the
battery connector. If it is loose,
securely connect the connector.
Always
1100H Memory card
access error
Data cannot be written to the memory
card because the write protect switch
is locked.
Continue Unlock the write protect switch of
the memory card.
Always
1120H SNTP clock
setting error
Time setting has failed when the CPU
module is powered on or reset.
Continue Check if the time is correctly set in
parameter.
Check if the specified SNTP
server is operating normally and
there is no failure on the network
accessing the SNTP server
computer.
At power-on, at
RESET
1124H Default
gateway/
gateway IP
address error
The default gateway is not set
correctly.
The gateway IP address is not set
correctly.
The default gateway/gateway IP
address (network address after the
subnet mask) is different from that of
the IP address of the own node.
Continue Correct the default gateway IP
address.
Set the same network address as
that of the IP address.
Parameter
information
Always
1128H Own node port
number error
The port number is incorrect. Continue Correct the port number. Always
1129H Open
specification
port number
error
The port number setting of the
external device is incorrect.
Continue Correct the port number of the
external device.
Always
112EH Connection
establishment
failed
A
connection could not be established
in the open processing.
Continue Check the operation of the
external device.
Check if the open processing has
been performed in the external
device.
Check and correct the port
number of the module, IP address/
port number of the external
device, and opening method.
When the firewall is set in the
external device, check if the
access is permitted.
Check if the Ethernet cable is
disconnected.
Always
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing