36 ERROR CODES
36.4 List of Error Codes
555
36
1166H TCP/IP send
failed
Data was not sent correctly with TCP/
IP.
Continue Check the settings for connection
with the external device.
Check the operation of the
external device or switching hub.
Since there may be congestion of
packets on the line, send data
after a certain period of time.
Check if the Ethernet
communication load is high
because of the Ethernet functions
being executed. Use the Ethernet
functions so that the
communication load is reduced.
Check if the connection cable is
disconnected.
Check that there is no connection
failure with the switching hub.
Execute a PING test. If the test
completes with an error, take an
action to correct the error.
Always
1167H Unsend data
send error
Unsent data found, but could not be
sent.
Continue Check the settings for connection
with the external device.
Check the operation of the
external device or switching hub.
Since there may be congestion of
packets on the line, send data
after a certain period of time.
Check if the Ethernet
communication load is high
because of the Ethernet functions
being executed. Use the Ethernet
functions so that the
communication load is reduced.
Check if the connection cable is
disconnected.
Check that there is no connection
failure with the switching hub.
Execute a PING test. If the test
completes with an error, take an
action to correct the error.
Always
1180H Redundant IP
address error
The same IP address has been set as
the system A IP address, system B IP
address, and/or control system IP
address
Network addresses of the system A IP
address, system B IP address, and
control system IP address are
different.
Continue Set different IP addresses for the
system A IP address, system B IP
address, and control system IP
address.
Set the same network address for
the system A IP address, system
B IP address, and control system
IP address.
Parameter
information
At power-on, at
RESET
1200H Module
moderate error
A moderate error has been notified
from the intelligent function module
connected.
Stop/
continue
Check the detailed information
(system configuration information)
of the error by executing module
diagnostics using the engineering
tool, identify the error module, and
eliminate the error cause.
System
configuration
information
Always
1210H An inter-module synchronous signal
error has been notified from the
intelligent function module connected.
Continue
1220H Another CPU
module
moderate error
A moderate error has been notified
from another CPU module.
Stop/
continue
Check the detailed information
(system configuration information)
of the error by executing module
diagnostics using the engineering
tool, identify the error module, and
eliminate the error cause.
Check the mounting status and
reset status of other CPU
modules.
System
configuration
information
Alwa
ys
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing