572
36 ERROR CODES
36.4 List of Error Codes
2440H Module major
error
In a multiple CPU system, the control
CPU setting in the system parameters
is different from that of other CPU
modules.
In a multiple CPU system, other CPU
modules (SIL2 Process CPU or
Safety CPU) have detected a
parameter verification error.
An error has been detected in the I/O
module or intelligent function module
during the initial processing.
Stop Correct the system parameter
settings for the CPU No.2 and
later in accordance with those of
the CPU No.1.
Eliminate the error cause of
another CPU module (Safety CPU
or SIL2 Process CPU).
Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
error module. Please consult your
local Mitsubishi representative.
System
configuration
information
At power-on, at
RESET
2441H Module major
error
An error has been detected in the I/O
module or intelligent function module
when the instruction was executed.
Stop/
continue
Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
error module. Please consult your
local Mitsubishi representative.
Error location
information,
system
configuration
information
At instruction
execution
2442H An error has been detected in the I/O
module or intelligent function module
during the END processing.
Stop/
continue
System
configuration
information
At module
access
2443H An error has been detected in the I/O
module or intelligent function module.
Stop
2450H Module major
error
A major error has been notified from
the intelligent function module
connected.
The I/O module or intelligent function
module is not mounted properly or
was removed during operation.
Stop/
continue
Take measures to reduce noise.
Check the connection status of the
extension cable.
Check the detailed information
(system configuration information)
of the error by executing module
diagnostics using the engineering
tool and check the module
corresponding to the displayed
slot number.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
error module. Please consult your
local Mitsubishi representative.
System
configuration
information
Always
2460H Another CPU
module major
error
An error has been detected in another
CPU module during the initial
processing.
Stop Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
host CPU module or another CPU
module where the error has been
detected. Please consult your
local Mitsubishi representative.
System
configuration
information
At power-on, at
RESET
2461H An error has been detected in another
CPU module when the instruction was
executed.
St
o
p/
continue
Error location
information,
system
configuration
information
At instruction
execution
2462H An error has been detected in another
CPU module during the END
processing.
Stop/
continue
System
configuration
information
At END
instruction
execution
2463H An error has been detected in another
CPU module.
Stop System
configuration
information
At power-on, at
RESET
2470H A major error has been notified from
another CPU module.
Stop/
continue
System
configuration
information
Always
2480H Multiple CPU
error
In a multiple CPU system, an error
has been detected in the CPU module
where "Stop" is set in the operation
mode setting parameter.
Any CPU module other than CPU
No.1 is mounted in the inapplicable
slot.
(An error occurs in the CPU module
mounted in the inapplicable slot.)
Stop Check the detailed information
(system configuration information)
of the error by executing module
diagnostics using the engineering
tool, identify the error module, and
eliminate the error cause.
Remove the CPU module from the
inapplicable slot.
System
configuration
information
Always
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing