EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R Series - Page 576

Mitsubishi Electric MELSEC iQ-R Series
760 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
574
36 ERROR CODES
36.4 List of Error Codes
24C3H System bus
error
An error was detected on the system
bus.
Stop CPU module
Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
CPU module, base unit, extension
cable, or module (I/O module or
intelligent function module)
connected. Please consult your
local Mitsubishi representative.
Redundant function module
The possible cause is malfunction
due to noise. Take measures to
reduce noise by checking the
distance of wires and cables, and
the grounding status of each
device.
Execute a module communication
test. If the same error code is
displayed again, the possible
cause is a hardware failure of the
redundant function module.
Please consult your local
Mitsubishi representative.
System
configuration
information
At module
access
24C4H System bus
error
An error was detected on the system
bus.
Stop Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
base unit, extension cable, or
module (I/O module or intelligent
function module) connected.
Please consult your local
Mitsubishi representative.
System
configuration
information
At module
access
24C5H
24C6H System bus
error
An error was detected on the system
bus.
Stop CPU module
Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
CPU module or extension cable.
Please consult your local
Mitsubishi representative.
Redundant function module
The possible cause is malfunction
due to noise. Take measures to
reduce noise by checking the
distance of wires and cables, and
the grounding status of each
device.
Execute a module communication
test. If the same error code is
displayed again, the possible
cause is a hardware failure of the
redundant function module.
Please consult your local
Mitsubishi representative.
At module
access
24C8H System bus
error
An error was detected on the system
bus.
Stop Take measures to reduce noise.
Reset the CPU module and run it
again. If the same error code is
displayed again, the possible
cause is a hardware failure of the
extension cable, or module (I/O
module or intelligent function
module) connected. Please
consult your local Mitsubishi
representative.
At power-on, at
RESET
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-R Series

Related product manuals