578
36 ERROR CODES
36.4 List of Error Codes
2840H File name
specification
error
The file specified in the instruction
does not exist.
Stop/
continue
Check the detailed information
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
Check the detailed information
(drive/file information) of the error
by executing module diagnostics
using the engineering tool, create
the specified file, and write it to the
CPU module. Or, set all the
required files in the CPU
parameters (file setting).
Error location
information,
drive/file
information
At instruction
execution
2841H File name
specification
error
The program file specified in the
instruction is not set in the CPU
parameters (program setting).
Stop/
continue
Check the detailed information
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
Check the detailed information
(drive/file information) of the error
by executing module diagnostics
using the engineering tool, and set
the specified program file in the
CPU parameter.
Error location
information,
drive/file
information
At instruction
execution
2842H File name
specification
error
A file that cannot be specified with the
instruction was specified.
Stop/
continue
Check the detailed information
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and correct the program.
Check the detailed information
(drive/file information) of the error
by executing module diagnostics
using the engineering tool, and
check the specified file.
Error location
information,
drive/file
information
At instruction
execution
3000H Boot function
execution error
The boot setting in the memory card
parameters is incorrect.
Stop Check and correct the boot setting
in the memory card parameters.
Drive/file
information
At power-on, at
RESET
3001H Boot function
execution error
When the boot function was
executed, the file format processing
failed.
Stop Reset the CPU module and
execute the boot function again. If
the same error code is displayed
again, the possible cause is a
hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
Drive/file
information
At power-on, at
RESET
3003H Boot function
execution error
When the boot function was
executed, the file passwords did not
match.
Stop Check and correct the file
password settings of the transfer
source and transfer destination
files.
Delete the boot setting.
Drive/file
information
At power-on, at
RESET
3004H Boot function
exec
uti
on error
When the boot function was
executed, the CPU built-in memory
capacity was exceeded.
Stop Check and correct the boot
setting.
Delete unnecessary files in the
CPU built-in memory.
Clear the CPU built-in memory by
selecting "Clear" to "Operation
Setting at CPU Built-in Memory
Boot" in the memory card
parameters, and execute the boot
function.
Drive/file
information
At power-on, at
RESET
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing

Table of Contents