582
36 ERROR CODES
36.4 List of Error Codes
3141H FB/FUN
program error
The structure of FB/FUN program is
incorrect.
Stop Take measures to reduce noise.
Write the sequence program(s)
and FB program(s) to the CPU
module again. Then, reset the
CPU module and run it again. If
the same error code is displayed
again, the possible cause is a
hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
Error location
information
At instruction
execution
3142H Temporary area
error
The temporary area was used
incorrectly.
Stop Check the detailed information
(error location information) of the
error by executing module
diagnostics using the engineering
tool, display the error program
(step) by clicking the [Error Jump]
button, and check the program.
Take measures to reduce noise.
Write the sequence program(s)
and FB program(s) to the CPU
module again. Then, reset the
CPU module and run it again. If
the same error code is displayed
again, the possible cause is a
hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
Error location
information
At instruction
execution
3160H
to
3163H
SFC program
block, step error
The SFC program configuration is
illegal.
Stop Take measures to reduce noise.
Write the SFC program to the
CPU module again. Then, reset
the CPU module and run it again.
If the same error code is displayed
again, the possible cause is a
hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
Error location
information
At power-on, at
RESET, at
STOP RUN
state, at SFC
program
execution
3170H SFC program
block, step error
The number of SFC program steps
exceeds the total number of step
relays (S).
Stop Correct the program so that the
number of SFC program steps
does not exceed the total number
of step relays (S).
Check and correct the number of
device setting step relays (S) in
the CPU parameters.
Error location
information
At power-on, at
RESET, at
STOP RUN
state, at SFC
program
execution
3171H SFC program
block, step error
The total number of SFC program
blocks (max. step No. + 1) exceeds
the total number of step relays (S).
Stop Correct the program so that the
total number of SFC program
blocks (max. step No. + 1) does
not exceed the total number of
step relays (S).
Check and correct the number of
device setting step relays (S) in
the CPU parameters.
Error location
information
At power-on, at
RESET, at
STOP RUN
state, at SFC
program
execution
3180H SFC program
configuration
error
T
he SFC program configuration is
illegal.
Stop Take measures to reduce noise.
Write the SFC program to the
CPU module again. Then, reset
the CPU module and run it again.
If the same error code is displayed
again, the possible cause is a
hardware failure of the CPU
module. Please consult your local
Mitsubishi representative.
Error location
information
At power-on, at
RESET, at
STOP RUN
state, at SFC
program
execution
3190H At SFC
program
execution
3191H
Error
code
Error name Error details and cause Stop/
continue
Action Detailed
information
Diagnostic
timing