36 ERROR CODES
36.4 List of Error Codes
611
36
413DH File related error The specified file capacity cannot be secured. Execute again after increasing the capacity of the specified
drive (memory).
413EH File related error Operation is disabled for the specified drive
(memory).
Execute again after changing the target drive (memory).
413FH File related error The file is inhibited to be written to the file storage
area.
Execute again after changing the specified drive (memory).
414AH Intelligent function module
specification error
In a multiple CPU system, operation was
performed to a non-controlled intelligent function
module or network module.
Execute the operation again from the control CPU of the
target module.
414CH Intelligent function module
specification error
The specified buffer memory address cannot be
accessed.
Execute again after checking the buffer address.
4150H File related error An attempt was made to initialize the drive
(memory) protected by the system.
Do not initialize the target drive (memory) as it cannot be
initialized.
4151H File related error An attempt was made to delete the file/folder
protected by the system.
Do not delete the target file as it cannot be deleted.
4160H Online registration error The registered number of I/O devices of the
forced on/off target exceeded the maximum.
Cancel the registration of I/O devices of the forced on/off
target that is not used.
4168H Online registration error The number of registered settings of the device
test with execution conditions has exceeded 32.
Disable the settings of the device test with execution
conditions registered in the CPU module. Alternatively,
reduce the number of executional conditioned device tests to
be registered at a time.
4169H Online registration error No settings of the device test with execution
conditions are registered.
Check the number of registered settings of the device test
with execution conditions in the CPU module, and disable the
settings.
416AH Online registration error The specified execution conditions do not exist.
(Device test with execution conditions)
Check whether the execution conditions (program block, step
No., and execution timing) specified for disabling settings are
registered in the CPU module.
416BH Online registration error Other than the ladder program was specified for
the registration of the device test with execution
conditions.
Check and correct the program block specified when the
settings of the device test with execution conditions are
registered or disabled.
41C1H File related error The format information data of the specified drive
(memory) is abnormal.
The file information data may be corrupted.
Back up data in the CPU module, and then initialize the
memory.
41C2H File related error File open specification data for file access is
wrong.
Execute again after checking the specification data.
41C3H File related error Simultaneously accessible files exceeded the
maximum.
Execute again after decreasing file operations.
41C4H File related error Simultaneously accessible files exceeded the
maximum.
Execute again after decreasing file operations.
41C5H File related error The specified file does not exist.
When CPU Module Logging Configuration Tool is
used
When an attempt was made to re-register the data
logging with the previous settings, the
corresponding file did not exist.
Execute again after checking the file.
41C7H File related error The specified file/folder or drive (memory) does
not exist.
Execute again after checking the file/folder or drive
(memory).
41C8H File related error The size of the specified file has exceeded that of
the existing file.
Execute again after checking the size of the specified file.
If the error recurs after re-execution, the file information data
may be corrupted.
Back up data in the CPU module, and then initialize the
memory.
41C9H File related error Access to the file sector has failed.
The format information data of the target drive
(memory) is abnormal.
Back up data in the CPU module, and then initialize the
memory.
41CAH File related error Access to the file sector has failed.
The format information data of the target drive
(memory) is abnormal.
Back up data in the CPU module, and then initialize the
memory.
41CBH File related error The file name is specified in a wrong method. Execute again after checking the file name.
Error
code
Error name Error details and cause Action