610
36 ERROR CODES
36.4 List of Error Codes
4121H File related error The specified drive (memory) or file does not
exist.
Execute again after checking the specified drive (memory) or
file.
4122H File related error The specified drive (memory) or file does not
exist.
Execute again after checking the specified drive (memory) or
file.
4123H File related error The specified drive (memory) is abnormal.
When CPU Module Logging Configuration Tool is
used
The data logging was started to the memory
having an error.
Initialize the memory, and restore the drive (memory) to its
normal state.
4124H File related error The specified drive (memory) is abnormal. Initialize the memory, and restore the drive (memory) to its
normal state.
4125H File related error The specified drive (memory) or file is performing
processing.
Execute again after a while.
4126H File related error The specified drive (memory) or file is performing
processing.
Execute again after a while.
4127H File related error File password mismatch Execute again after checking the file password.
4128H File related error File password mismatch with copy destination Execute again after checking the file password.
4129H File related error The request cannot be executed since the
specified drive (memory) is ROM.
Execute again after changing the target drive (memory).
412AH File related error The request cannot be executed since the
specified drive (memory) is ROM.
Execute again after changing the target drive (memory).
412BH File related error The specified drive (memory) is write-inhibited. Execute again after changing the write inhibit condition or
drive (memory).
412CH File related error The specified drive (memory) is write-inhibited. Execute again after changing the write inhibit condition or
drive (memory).
412DH File related error The specified drive (memory) does not have
enough free space.
Execute again after increasing the free space of the drive
(memory).
412EH File related error The specified drive (memory) does not have
enough free space.
Execute again after increasing the free space of the drive
(memory).
412FH File related error The drive (memory) capacity differs between the
drive (memory) copy destination and copy
source.
Execute again after checking the drive (memory) copy
destination and copy source.
4130H File related error The drive (memory) type differs between the
drive (memory) copy destination and copy
source.
Execute again after checking the drive (memory) copy
destination and copy source.
4131H File related error The file name of the file copy destination is the
same as that of the copy source.
Execute again after checking the file names.
4132H File related error The specified number of files does not exist. Execute again after checking the specified data.
4133H File related error The specified drive (memory) has no free space. Execute again after increasing the free space of the drive
(memory).
4134H File related error The attribute specification data of the file is
wrong.
Execute again after checking the specified data.
4135H File related error The date/time data of the engineering tool
(personal computer) is out of range.
Execute again after checking the clock setting of the
engineering tool (personal computer).
4136H File related error The specified file already exists. Execute again after checking the specified file name.
4137H File related error The specified file is read-only. Execute again after changing the condition of the specified
file.
4138H File related error Simultaneously accessible files exceeded the
maximum.
Execute again after decreasing file operations.
4139H File related error The size of the specified file has exceeded that of
the existing file.
Execute again after checking the size of the specified file.
413AH File related error The specified file has exceeded the already
existing file size.
Execute again after checking the size of the specified file.
413BH File related error The same file was simultaneously accessed from
different engineering tools.
When CPU Module Logging Configuration Tool is
used
An operation was performed to a file being
accessed.
Execute again after a while.
413CH File related error The specified file is write-inhibited. Execute again after changing the file condition.
Error
code
Error name Error details and cause Action