1 FUNCTIONS
1.1 BACnet Object Function
OutOfService property
The value of an OutOfService property can be set using a program
*1
. The value can also be set by using a
WriteProperty(Multiple) service or a configuration function.
The value of an OutOfService property is the logical sum of the value set with a program and the value set with a
WriteProperty(Multiple) service or a configuration function.
*1 Set a value by storing '1' (True) or '0' (False) to the OutOfService of a CONTROL in the buffer memory using a program.
Value set with program
*1
. Value set with WriteProperty service/configuration function Value of OutOfService
property
1True True
1False True
0True True
0False False