124
1 FUNCTIONS
1.4 BACnet Request Function (Read Function)
1.4 BACnet Request Function (Read Function)
This function reads property values from a BACnet module or another BACnet device.
A BACnet module sends a ReadPropertyMultiple service to the read target property set to a data block (access block for
reading).
The property values of the data types described in the following section can be read.
Page 289 PrimitiveDataType
How to use the read function
Operating procedure
1. Select [Maintenance] [Pause/Restart], and click the [Pause] button on the "Pause/Restart" screen.
2. Select [Settings] [BACnetRequest] [Read], and click the [Add] button.
3. Specify "BufferMemoryAddress" and "Qty." of a data block (access block for reading).
*1
Specify an even number within the range of 256 to 32767 (100h to 7FFFh).
To specify a buffer memory address in hexadecimal, add 'h' at the end of it.
When '0' is specified to the buffer memory address, the data blocks are automatically assigned to the free space in the buffer
memory.
*1 For the method to assign multiple data blocks in a batch, refer to the following section.
Page 207 Assigning data blocks using a CSV file