1 FUNCTIONS
1.1 BACnet Object Function
Keiryo object
This object is used for reading scaling values (electrical energy, water dosage, etc.) from a programmable controller system to
a BACnet device.
List of properties
The following shows the properties supported by Keiryo objects.
Additionally, the availability of reading/writing data from/to a BACnet device is shown in the following table.
R: Read-only, W: Write-only, R/W: Read/Write
PropertyID Property Data type R/W Remarks
0 AckedTransitions BitString R/W
17 NotificationClass Unsigned R/W
28 Description CharacterString R/W
31 DeviceType CharacterString R/W
35 EventEnable BitString R/W
36 EventState Enumerated R
52 LimitEnable BitString R/W
72 NotifyType Enumerated R/W
75 ObjectIdentifier BACnetObjectIdentifier R
77 ObjectName CharacterString R/W
79 ObjectType Enumerated R
81 OutOfService BOOLEAN R/W
85 PresentValue Unsigned R/W
103 Reliability Enumerated R
111 StatusFlags BitString R
117 Units Enumerated R/W
520 MaxCountValue Unsigned integer R/W
521 Weight Real number R/W
522 ValueSet(J) Unsigned integer R/W
523 ValueBeforeChange(J) Unsigned integer R/W
524 ValueChangeTime(J) BACnetDateTime R/W
525 LimitMonitoringInterval(J) Unsigned integer R/W
526 AccumulatedCountHighLimit Unsigned integer R/W
527 ListOfCounterData ListOfHistoricalData R/W
530 LastListOfCounterDataAdded BACnetDateTime R
9002 IntrinsicEventDisable BOOLEAN R/W BACnet module proprietary properties
Page 270 Details of BACnet Module
Proprietary Properties
9003 UnsolicitedCOV Enumerated R/W
9006 COVSendInterval Unsigned R/W