Appendix 6 BACnet Detail Setting List
Interaction
Parameters for the BACnet monitoring function, COV interaction function, and Event interaction function can be set in
"Interaction".
For the setting method, refer to the following section.
Page 279 Setting method
*1 The data of a COV notification is as follows:
Value of PresentValue property
Value of StatusFlags property
*2 The data of an Event notification is as follows:
EventState
PresentValue (When a PresentValue is included in a packed by the send source BACnet device of an Event notification.)
StatusFlags (When a StatusFlags is included in a packed by the send source BACnet device of an Event notification.)
Who-Is
Parameters for recognizing another BACnet device as a communication target can be set in "Who-Is".
For the setting method, refer to the following section.
Page 279 Setting method
Item Description Initial
value
Data range
RecDataOverwriteMonitor Set whether to overwrite the Data of an access block for BACnet monitoring every time when
receiving data with the BACnet monitoring function.
0: Data is not overwritten. Data is output only when '0' is stored to the CONTROL. When '1' is
stored, received data is discarded.
1: Data is overwritten regardless of the value of a CONTROL.
00 to 1
RecDataOverwriteCOVLink When '1' is set to a MonitorDataSetByCOV, set whether to overwrite the Data of an access
block for BACnet monitoring every time when receiving a COV notification.
0: Data is not overwritten. Data is output only when '0' is stored to the CONTROL. When '1' is
stored, received data is discarded.
1: Data is overwritten regardless of the value of a CONTROL.
00 to 1
RecDataOverwriteEventLink When '1' is set to a MonitorDataSetByEvent, set whether to overwrite the Data of an access
block for BACnet monitoring every time when receiving an Event notification.
0: Data is not overwritten. Data is output only when '0' is stored to the CONTROL. When '1' is
stored, received data is discarded.
1: Data is overwritten regardless of the value of a CONTROL.
00 to 1
MonitorDataSetByCOV Set whether to write the COV notification data
*1
received from the monitoring target set to
[Setting] [BACnetMonitor] to an access block for BACnet monitoring.
0: Information is not written.
1: Information is written.
10 to 1
MonitorDataSetByEvent Set whether to write the Event notification data
*2
received from the monitoring target set to
[Setting] [BACnetMonitor] to an access block for BACnet monitoring.
0: Information is not written.
1: Information is written.
10 to 1
MaxScanPropertyCount Set the maximum number of properties which can be read in a batch to a
ReadProperty(Multiple) service that is sent when using the BACnet monitoring function.
80 0 to
2147483647
Item Description Initial
value
Data
range
WhoisInitiatorMode Set whether to send Who-Is services with the interval set to the WhoisSendInterval parameter.
0: A request is sent with the set interval.
1: A request is not sent periodically. Turn Y6 ON with an arbitrary timing to send Who-Is services.
1 0 to 1
WhoisSendInterval Set a send interval to send Who-Is services. (Unit: seconds) 60 0 to 600
CheckAliveInterval When monitoring I-Am services from another BACnet device, set the cycle. (Unit: seconds)
When do not monitor, set '0'.
180 0 to 600
SystemStatusReadInterval When reading a SystemStatus property value of another BACnet device periodically, set the
cycle. (Unit: seconds)
When do not monitor, set '0'.
0 0 to 600
AutoAddressBindingSetDisable Set whether to automatically recognize a device as a communication target when an I-Am service
is received from another BACnet device.
0: An I-Am service is received to automatically recognize the device.
1: A device is not automatically recognized as a communication target even when an I-Am service
is received. To recognize the device, set with a BACnet device.
0 0 to 1