150
1 FUNCTIONS
1.7 COV Interaction Function
Execution example of the COV interaction function
This section shows an execution example of the COV interaction function which receives COV notifications from an
AnalogInput object (instance number: 10) in another BACnet device (device instance number of a device: 3).
Assignment of an access block for COV interaction
Assign an access block for COV interaction in [Settings] [COV Interaction] as follows.
For the assignment method, refer to the operating procedure from 1 to 4 described in the following section.
Page 146 How to use the COV interaction function
Item Description
DeviceInstanceNo 3
ObjectID ObjectType: AnalogInput, instance number: 10
BufferMemoryAddress 600
Disable Do not select.
Periodic SubscribeCOV transmission Select this item.
ProcessID 1
Confirmed/Unconfirmed Confirmed COV Notification
LifeTime 480