APPX
Appendix 5 CSV File Format
277
A
CSV file for the COV interaction function
If a value outside the range is set, the data in the corresponding row will not be added and overwritten to a BACnet module.
*1 The RWordAddress is handled as a word address by default.
If other than "RWordAddress" is entered to the column comment, the buffer memory address will be handled as a byte address.
CSV file for the Event interaction function
If a value outside the range is set, the data in the corresponding row will not be added and overwritten to a BACnet module.
*1 The RWordAddress is handled as a word address by default.
If other than "RWordAddress" is entered to the column comment, the buffer memory address will be handled as a byte address.
Column
No.
Column
comment
Description of data row Value to be set
1 DeviceInstanceNo Instance number of a COV notification send
source device
Range: 0 to 4194303
To receive COV notifications which are sent from a BACnet module,
set the instance number of the BACnet module.
For the instance number of a BACnet module, refer to the following
section.
Page 198 Setting an instance number and a BACnet standard
2 ObjectType Object type number of a COV notification send
source object
Range: 0 to 1023
3 ObjectInstanceNo Instance number of a COV notification send
source object
Range: 0 to 4194303
4RWordAddress
*1
Buffer memory address of an access block for
COV interaction
0: A free space is assigned. If there is no free space, a data block is
not assigned.
Other than 0: Specify a buffer memory address in decimal. If a part of
the set buffer memory address has already been used, a data block
will not be assigned.
5 SubscribeCOVEnabl
e
Enable SubscribeCOV. 0: Disable
1: Enable
6 ProcessID ProcessID Range: 1 to 4294967295
7 Confirm Confirmed/Unconfirmed 0: Unconfirmed
1: Confirmed
8 LifeTime Cycle to read values (minutes) Range: 1 to 1440
Column
No.
Column
comment
Description of data row Value to be set
1 DeviceInstanceNo Instance number of an Event notification send
source device
Range: 0 to 4194303
To receive Event notifications which are sent from a BACnet module,
set the instance number of the BACnet module.
For the instance number of a BACnet module, refer to the following
section.
(Page 198 Setting an instance number and a BACnet standard)
2 ObjectType Object type number of an Event notification
send source object
Range: 0 to 1023
3 ObjectInstanceNo Instance number of an Event notification send
source object
Range: 0 to 4194303
4RWordAddress
*1
Buffer memory address of an access block for
Event interaction
0: A free space is assigned. If there is no free space, a data block is
not assigned.
Other than 0: Specify a buffer memory address in decimal. If a part of
the set buffer memory address has already been used, a data block
will not be assigned.