1 FUNCTIONS
1.4 BACnet Request Function (Read Function)
129
1
Creation of a program
Create a program to store the following data in a read target BACnet device to an access block for reading: instance number
of a destination device, ObjectIdentifier of an object, PropertyIdentifier and ArrayIndexe (up to 4).
Values to be stored to an access block for reading
For details on the format of access blocks for reading, refer to the following section.
Page 291 Format of access blocks for reading
Offset
(Decimal address)
Name Value to be stored
+0
(300)
CONTROL Store '1' (send request) when sending a
ReadPropertyMultiple(ReadProperty) service.
+1
(301)
STATUS (No settings)
+2 to +3
(302 to 303)
Instance number of a destination device 3 (instance number of read target device)
+4 to +5
(304 to 305)
ObjectIdentifier K10 (Ah)
b32 to b22: 0 (object type number of an AnalogInput)
b21 to b0: 10 (instance number of an object)
For the ObjectIdentifier, refer to Point in the following section.
Page 19 List of objects
+6
(306)
Property-1 PropertyIdentifier 85 (PropertyIdentifier of a PresentValue)
+7
(307)
ArrayIndex FFFFh
+8
(308)
Read data 4 (The data type of the PresentValue of an AnalogInput object is REAL.)
+9
(309)
0 (No priority)
+10 to +11
(310 to 311)
(No settings)
+12
(312)
Property-2 PropertyIdentifier FFFFh
+13
(313)
ArrayIndex (No settings)
+14 to +17
(314 to 317)
Read data (No settings)
+18
(318)
Property-3 PropertyIdentifier FFFFh
+19
(319)
ArrayIndex (No settings)
+20 to +23
(320 to 323)
Read data (No settings)
+24
(324)
Property-4 PropertyIdentifier FFFFh
+25
(325)
ArrayIndex (No settings)
+26 to +29
(326 to 329)
Read data (No settings)