1 FUNCTIONS
1.5 BACnet Request Function (Write Function)
137
1
Creation of a program
Write the following data in a write target BACnet device to the access block for writing which is assigned to the buffer memory
using a program: instance number of a destination device, ObjectIdentifier of an object, PropertyIdentifier and ArrayIndex (up
to 4).
Values to be stored to an access block for writing
For details on the format of access blocks for writing, refer to the following section.
Page 292 Format of access blocks for writing
Offset
(Decimal address)
Name Value to be stored
+0
(400)
CONTROL Store '1' (send request) when sending a
WritePropertyMultiple(WriteProperty) service.
+1
(401)
STATUS (No settings)
+2 to +3
(402 to 403)
Instance number of a destination device 3 (instance number of a write target device)
+4 to +5
(404 to 405)
ObjectIdentifier K4194314 (40000Ah)
b32 to b22: 1 (object type number of AnalogOutput)
b21 to b0: 10 (instance number of an object)
For the ObjectIdentifier, refer to Point in the following section.
Page 19 List of objects
+6
(406)
Property-1 PropertyIdentifier 85 (PropertyIdentifier of a PresentValue)
+7
(407)
ArrayIndex FFFFh
+8
(408)
Write data 4 (The data type of the PresentValue of an AnalogOutput object is
REAL.)
+9
(409)
0 (No priority)
+10 to +11
(410 to 411)
E1 (real number 1.0)
+12
(412)
Property-2 PropertyIdentifier FFFFh
+13
(413)
ArrayIndex (No settings)
+14 to +17
(414 to 417)
Write data (No settings)
+18
(418)
Property-3 PropertyIdentifier FFFFh
+19
(419)
ArrayIndex (No settings)
+20 to +23
(420 to 423)
Write data (No settings)
+24
(424)
Property-4 PropertyIdentifier FFFFh
+25
(425)
ArrayIndex (No settings)
+26 to +29
(426 to 429)
Write data (No settings)