1 FUNCTIONS
1.1 BACnet Object Function
97
1
Buffer memory format of GeneratorLoadControl objects
The following shows the format of properties assigned to the buffer memory.
Additionally, the availability of reading from/writing to a CPU module is shown in the following table.
R: Read-only, W: Write-only, R/W: Read/Write
Offset Name Remarks R/W
+0 CONTROL b15 OutOfService 0: False, 1: True
When '1' is set to "OutOfServiceControl" in [Settings] [Basic
Information] [BACnet Detail Setting] button "Interface", the
value of an OutOfService property is stored.
R/W
b14 to b4 Not used
b3 to b0 Reliability 0: NoFaultDetected
1: NoSensor
2: OverRange
3: UnderRange
4: OpenLoop
5: ShortedLoop
6: NoOutput
7: UnreliableOther
8: ProcessError
9: MultiStateFault
10: ConfigurationError
+1 STATUS b15 to b14 Not used R
b13 to b11 EventState 0: Normal
1: Fault
2: Offnormal
3: HighLimit
4: LowLimit
5: LifeSafetyAlarm
b10 AckedTransition ToOffnormal 0: False, 1: True
b9 ToFault 0: False, 1: True
b8 ToNormal 0: False, 1: True
b7 Not used
b6 EventEnable ToOffnormal 0: False, 1: True
b5 ToFault 0: False, 1: True
b4 ToNormal 0: False, 1: True
b3 StatusFlags InAlarm 0: False, 1: True
b2 Fault 0: False, 1: True
b1 Overridden Always 0
b0 OutOfService 0: False, 1: True
+2 PresentValue The current value of a generator load control level is stored.
1 to 16
R/W
+3 Not used
+4 to +5 Target_Value_To_Supply The target value to provide an electric power generated by a
generator is stored.
R/W
+6 to +7 Adjust_Value_Of_Load The adjusted electric power, which is obtained by subtracting the
currently supplied electric power from a Target_Value_To_Supply,
is stored.
R/W
+8 to +9 Level_Value[1] The amount of adjusted electric power for each level of a
generator load control level is stored.
R/W

+38 to +39 Level_Value[16]