10 FUNCTIONS
10.1 SIL2 Mode
259
10
6. Select the check box for the R60AD8-G (Main) to be enabled, and click the [Update] button. The current enabled/
disabled status of the SIL2 analog input system is displayed for "Module Status".
Module Status Description
The information is not acquired.
Valid The safety module is enabled and the configured parameters are valid.
Invalid The safety module is not enabled and the configured parameters are not valid.
Valid (Reset Wait) The safety module has just been enabled. In this state, the R60AD8-G needs to be reset, and the module
status will be enabled after the reset. At this time, the ALM LED flashes every 0.4 seconds.
Invalid (Reset Wait) The safety module has just been disabled. In this state, the R60AD8-G needs to be reset, and the module
status will be disabled after the reset. At this time, the ALM LED flashes every 0.4 seconds.
Timeout A timeout occurred because no response was returned from the target module. Check the settings or status
of the target module. ( Page 314 When "Timeout" is displayed for "Module Status")
Is the module set to SIL2 mode?
Has an error occurred?