248
9 INSTALLATION AND WIRING
9.2 External Wiring
Precautions for channel number and output signal
Before wiring for SIL2 mode, pay attention to the following points.
Precautions for channel number
All the channels used for the R60AD8-G (Main), R60AD8-G (Sub), and R60DA8-G for diagnostics should use the same
channel number.
Ex.
When the R60AD8-G (Main) and R60AD8-G (Sub) use CH1 to make A/D conversion, the R60DA8-G for diagnostics must use
CH1.
Precautions for output signal
When a relay is wired with the RY40PT5B, the output signals used for the RY40PT5B should be wired as follows.
Ex.
When the R60AD8-G (Main) and R60AD8-G (Sub) use CH1, wire the R60AD8-G (Main) to Y0 of the RY40PT5B and wire the
R60AD8-G (Sub) to Y1 of the RY40PT5B.
Output signals used
for the RY40PT5B
Channel used by the R60AD8-G
CH1 CH2 CH3 CH4 CH5 CH6 CH7 CH8
R60AD8-G (Main) side Y0 Y2 Y4 Y6 Y8 YA YC YE
R60AD8-G (Sub) side Y1 Y3 Y5 Y7 Y9 YB YD YF