306
14 TROUBLESHOOTING
14.2 Checking the State of the Module
14.2 Checking the State of the Module
The following functions are available in the "Module Diagnostics" window of the R60AD8-G.
Error Information
Check the description and the actions of the errors that have occurred.
[Diagnostics] [System Monitor] Right-click the target module. [Module Diagnostics]
Function Application
Error Information Displays the details of the currently occurring error.
Clicking the [Event History] button displays the errors that have occurred on
the network and the history of the errors detected and the operations
executed on each module.
Module Information List Displays each status information of the R60AD8-G.
Item Description
Status Major: An error such as a hardware failure or memory failure. The module stops operating.
Moderate: An error, such as a parameter error, which affects module operation. The module stops
operating.
Minor: An error such as a communication failure. The module continues operating.
Detailed Information Displays detailed information about each error (maximum of 3 pieces).
Cause Displays the details of the cause of each error.
Corrective Action Displays actions against the error.