286
10 FUNCTIONS
10.8 SIL2 A/D Conversion Function
A/D conversion circuit diagnostic function
The R60DA8-G for diagnostics regularly inputs an analog value to the R60AD8-G set to SIL2 mode to internally diagnose the
A/D conversion circuit of the R60AD8-G.
Internal diagnostics is executed at the following timing.
When the entire system starts operating normally after power-on (at start-up)
In the cycle specified by "A/D conversion circuit diagnostic cycle setting" (during operation)
This function uses the SIL2 safety program FB (M+SIL2ADG_ADConv_R) and SIL2 standard program FB (M+SIL2ADG-
IEF_WriteDAVal_R).
During operation, A/D conversion circuit diagnostics is executed paired with the double input discrepancy
detection function.
If system switching occurs during A/D conversion circuit diagnostics, the A/D conversion circuit diagnostics
is suspended, and after the system switching is complete, the diagnostics is resumed at the point where it
was suspended.
When the safety operation mode of SIL2 Process CPU is TEST MODE, the start-up A/D conversion circuit
diagnostics can be skipped by turning on i_bInitDiagSkip (start-up diagnostics skip request) of the SIL2
safety program FB (M+SIL2ADG_ADConv_R).
Setting procedure
To use the A/D conversion circuit diagnostic function, the following module parameter setting and a program by the SIL2
diagnostic FB library are required.
"A/D conversion circuit diagnostic cycle setting"
"A/D conversion circuit diagnostic cycle setting"
Set a cycle to perform A/D conversion circuit diagnostics.
[Navigation window] [Parameter] [Module Information] [R60AD8-G(S2M)] [Module Parameter] [Application
setting] [A/D conversion circuit diagnostic cycle setting]
Program by the SIL2 diagnostic FB library
With a project on the SIL2 Process CPU side, create a safety program and standard program and define the I/O of the SIL2
diagnostic FB library. Refer to the following to create programs.
Page 297 EXAMPLE OF OPERATION
Item Setting range
A/D conversion circuit diagnostic cycle setting 60 to 480min