10 FUNCTIONS
10.4 A/D Conversion Enable/Disable Setting Function
10.4 A/D Conversion Enable/Disable Setting Function
This function controls whether to enable or disable the A/D conversion for each channel. Disabling the A/D conversion for
unused channels reduces the conversion cycles.
Setting procedure
Set "A/D conversion enable/disable setting" to "A/D conversion enable" or "A/D conversion disable".
[Navigation window] [Parameter] [Module Information] Module model name [Module Parameter] [Basic
setting] [A/D conversion enable/disable setting function]
10.5 A/D Conversion Method
An A/D conversion method can be set for each channel.
Sampling processing
This function converts analog input values to digital operation values at every sampling period.
The sampling period is "Conversion speed (12ms) Number of conversion enabled channels".
Whether to enable or disable the A/D conversion can be set for each channel. Disabling the A/D conversion
for unused channels reduces the conversion cycles.
Conversion cycle that applies when CH1 to CH3 is set to A/D conversion enabled
•12 3 = 36 (ms)
The conversion cycle is 36 (ms).
Analog input values are converted to digital operation values of CH1 to CH3 every 36ms.